Yellow Jacket - Digital Refrig.System Analyzer - NEW
Yellow Jacket Digital Refrigeration System Analyzer
This item is on sale for $649.00(regular price $792.49)
For time saving diagnostics, the easy-to-read pressured bar graphs of this patented unit quickly tell you more than you could ever see with the vibrating needle of a typical pressure gauge.
* Profiles 23 common refrigerants:
R-12, 22, 134a, 290, 401A, 401B, 402A, 402B, 404A, 406A, 407C, 408A, 409A, 410A, 414B, 416A, 417A, 420A, 422A, 502, 507, 508B, 600A (Upgradeable probe for new refrigerants)
* Integrated temperature probe for automatic superheat and subcooling readings
* Max and min pressure monitoring for control set-up
* Auto zero key to eliminate manual recalibration
* Easy-to-read LCD screen with large 3/8" digits
* Rugged case construction with rubber boot to tolerate impact and resist typical oils, acids, and sunlight
* Bar graph segments shows changes from digital reading (range of ±2 psi on low side, ±8 psi on high side)
* Digital readings show resolution of 1/4 psi on low side, 1 psi on high side
* Temperature in middle is corresponding bubble and dew points for current pressures
* Temperature, superheat or subcooling shown on lower right (eg. 14°F superheat)
* Pressure accuracy: 0.5% F.S. ± 1 least significant digit, calibration traceable to NIST
* Pressure ports: Two 1/8" acting as low and high side gauges
* Working pressure: Low side: 0-200 psi (1350 kPa, 13.5 bar) High side: 0-550 psi (3790 kPa, 37.9 bar)
* Proof pressure: Low side: 600 psi (4100 kPa, 41 bar)
High side: 1500 psi (10300 kPa, 103 bar)
* Temperature sensor range: -40° to 250°F (-40° to 125°C)
* Temperature accuracy: ±0.9°F (±0.5°C) between 32° to 158°F (0° to 70°C)
* Usage environment: Indoor/Outdoor dew, splash and rain resistant; do not immerse in water
* Storage and operational temperature: -4° to 122°F (-20° to 50°C)
* Power supply: 9V (approx. 6 months under normal use)
* Dimensions: 6.7" x 4.8" x 2.5" (17 cm x 12.2 cm x 6.4 cm)
Includes Titan four-valve aluminum manifold with hoses, temperature probe, two 1/8" swivel adapters and manual